oil pump
power transformer oil pump-disk type
1. inlet and outlet are at a right angle of 90°;
2. driven by disc motor, the axial dimension is short, the starting torque is large, the starting time is short, but the starting current is too large;
3, can use four-stage, six-stage motor, suitable for oil air, oil water cooler;
4, using centrifugal impeller
flow range: 30m3/h~150m3/h, delivery head range: 1m~15m
use conditions
ambient temperature: -25 ℃ ~ 40 ℃
transmission medium: transformer oil
the highest oil temperature of transformer oil inlet is 95 ℃,
the lowest is 5 ℃ higher than transformer oil freezing point.
it works by s1 continuous operation.
the rotation direction of the pump is clockwise.